Research Article

Experimental Harmonics Analysis of UPS (Uninterrupted Power Supply) System and Mitigation Using Single-Phase Half-Bridge HAPF (Hybrid Active Power Filter) Based on Novel Fuzzy Logic Current Controller (FLCC) for Reference Current Extraction (RCE)

Table 1

Different UPS System Efficiency and THD Result from experimental analysis

UPS systemEfficiencyTHD
U.P.SBatteryPowerCharging (%)Discharging (%)Charging
Voltage VWatt

U.P.S#1128007963.5.030.6
U.P.S#212550807070.5
U.P.S#324650768615.5
U.P.S#424160084.777.525.1
U.P.S#52412007886.521.5
U.P.SAverage THD32.63%