Abstract

The main purpose of this study, which was conducted within the framework of a DPC-ReLUIS research project, was to investigate the behaviour of a scaled isolated structure equipped with an in-parallel combination of steel-PTFE sliding bearings and elastomeric bearings (HDRBs). For this purpose, dynamic tests on shaking table were carried out at the Laboratory of the Department of Structures for Engineering and Architecture of the University of Naples Federico II, Italy. An available prototype steel framed structure was used as a superstructure. A further objective of this study was to evaluate the reliability of different analytical models of the isolation system, commonly used, in order to adequately simulate the dynamic response of the isolated structure. The effectiveness of the isolation system was evaluated comparing the experimental response of the isolated structure with the numerical response of the fixed-base structure.

1. Introduction

Base-isolation of a structure subjected to an earthquake allows a considerable reduction of the horizontal loads transmitted to the superstructure (Naeim and Kelly [1]). The following isolation strategies, or a suitable combination of them, can be used (Braga et al. [2]): increase of the fundamental vibration period of the structure (e.g., using elastomeric bearings), to shift it in the range of low spectral accelerations; limitation of the maximum force transmitted to the superstructure (e.g., using steel-PTFE sliding bearings with plane/curved surface or damping devices). Different isolation systems were studied by many authors (e.g., Dolce et al. [3]; Ponzo et al. [4]; Sorace et al. [5]). The nonlinear dynamic response of different base-isolated framed structures was studied in previous works (Mazza and Vulcano [6, 7]; Mazza et al. [8]).

This study was conducted within the framework of Task 2.3.2 of DPC-ReLUIS 2010–2013 research project aiming to experimentally validate the effectiveness of different isolation systems for a building structure. For this purpose, different scaled isolated structures were designed for an available prototype steel framed structure, assumed to be the superstructure. A wide experimental campaign was conducted for scaled isolated structures subjected to dynamic tests on shaking table at the Laboratory of the Department of Structures for Engineering and Architecture of the University of Naples Federico II, Italy. More precisely, the main purpose of this study was to investigate the behaviour and effectiveness of base-isolated structures in case an in-parallel combination of elastomeric bearings (HDRBs) and plane steel-PTFE sliding bearings is used. The reliability of different analytical models of the isolation system which are commonly used in simulating the dynamical response was evaluated comparing experimental and numerical results. The effectiveness of the isolation system was also evaluated, comparing the experimental response of the isolated structure with the numerical response of the fixed-base structure.

2. Description of Superstructure and Bearings

The 1/3 scaled steel frame model shown in Figure 1 was considered to be the superstructure. Its main properties are summarized below:(i)Plan dimensions are 2650 mm × 2150 mm, with a total height of about 2900 mm.(ii)The columns have welded square hollow sections (150 mm × 150 mm × 15 mm).(iii)Beams have rolled square hollow sections (120 mm × 120 mm × 12.5 mm).(iv)Pin connections were used between beams and columns.(v)The roof of the structure, supporting a reinforced concrete slab, had a mass of 4.1 tons, and the total mass of the superstructure was 5.35 tons.(vi)The fundamental period of the fixed-base structural model was about 0.26 s (Magliulo et al. [9]), which, considering the scale factor, corresponds to 0.45 s (this may be intended to be the fundamental period expected for a four-storey steel framed structure).(vii)The damping ratio was about 0.65%, according to free vibration decay method [9].Four steel-PTFE sliding bearings and two elastomeric isolators (HDRBs), all with circular cross section, were manufactured and provided by FIP Industriale S.p.A. (Padova, Italy). The main geometric and manufacturing characteristics of the bearings are illustrated in Figure 2 and Tables 1 and 2.

A small size of a sliding bearing (diameter of the PTFE-slider ϕ = 60 mm) was chosen to have a pressure sufficiently high (about 7.5 N/mm2) to avoid reaching a very high value of the friction coefficient. Because the motion for the tests was foreseen in one direction, two elastomeric bearings only were considered to limit their cost.

On the basis of many tests performed by the manufacturer on similar devices, a friction coefficient of 6% was assumed for a PTFE-slider. Moreover, each elastomeric bearing was produced to have a (secant) horizontal stiffness = 0.22 kN/mm at a displacement of ±130 mm, corresponding to a shear strain of 100% and equivalent viscous damping of about 15%. The above displacement was assumed to be that corresponding to the collapse of the elastomeric bearing.

3. Characterization Tests of the Isolation System

3.1. Experimental Set-Up and Instrumentation

To isolate the superstructure described above, the four sliding bearings, previously lubricated, were placed under the corners of the (horizontal) frame at the base of the superstructure, with the vertical axis correspondent to the axis of a column (Figures 3(a) and 3(b)). Each of the two elastomeric bearings was placed on the external side corresponding to the middle of a girder of the base frame having the axis parallel to the direction of motion imposed to the shaking table for the tests (Figure 3(c)). Main details of the connection of the bearings to the shaking table and a vertical view of the bearings are shown in Figure 4. An added mass, made up of concrete blocks having a total weight of 33.2 kN, was placed and connected to the horizontal frame at the base of the superstructure. All the weights and corresponding masses are reported in Table 3. Plan views of the added mass at the base and concrete slab at the top of the superstructure are represented in Figures 5(a) and 5(b), respectively.

The isolated steel frame model aimed to simulate a 1/3 scaled isolated structure. An approximated value of the fundamental period of the isolated structure model was obtained idealizing the isolated structure as a single-degree-of-freedom (SDOF) system. The total mass being equal to 8.56 kNs2/m (see Table 3) and the (secant) stiffness of the isolation system practically being equal to the total secant stiffness of the two elastomeric bearings, that is, 0.44 kN/mm (neglecting the contribution of the sliding bearings), the period of the scaled isolated structure was evaluated as about 0.87 s. Considering the scale factor, this corresponds to a period of an isolated structure of about 1.51 s that is 3.35 times the period of the fixed-base structure (0.45 s).

Many kinds of transducers, as specified in Table 4, were used and arranged in plan as shown in Figure 5 on the shaking table platform and base frame and at the top of superstructure. In particular, the laser-displacement sensors, connected to an external reference steel frame, measured the absolute displacements in the direction of the applied motions, while the triaxial accelerometers measured the acceleration components.

3.2. Dynamic Tests

To characterize the isolation system, different shaking table tests of the isolated structure were carried out studying the free vibrations following a steady-state harmonic motion of the table. Frequency and peak acceleration of the shaking table during the tests are reported in Table 5. Acceleration and displacement measured during test 4 are shown in Figure 6. The corresponding relative displacements of the isolated system and superstructure, measured on both sides of the base frame (see location of sensors W4 and W6 in Figure 5(a)), proved a practical symmetry of the motion (Figure 7).

It should be noted that it has been considered more realistic to simulate the dynamic response of the entire isolated structural system (instead of considering the response of the single device), because of the uncertainties in the connections between the single parts constituting the isolation system.

3.3. Characterization by Viscoelastic Model

On the basis of the above shaking table tests, it was possible to characterize the isolation system. For this purpose, the isolated structure was idealized as the two-degree-of-freedom (2-DOF) system shown in Figure 8, where: and represent the masses supposed to be lumped at the top and base floor levels of the superstructure, respectively; was the elastic (lateral) stiffness of the steel superstructure, while represented the equivalent stiffness of the isolation system.

With reference to the free vibrations following the steady-state forced phase, it was possible to identify (Table 6):(i)period of the isolated structure (experimentally);(ii)damping factor (), as average of the values obtained by the logarithmic decrement of damping considering the decay experimentally measured in different cycles;(iii)the equivalent stiffness of the isolation system, evaluated considering the (undamped) free vibrations of the 2-DOF system.The points representing the equivalent stiffness of (half) isolation system versus the maximum relative displacement of the same system reached in many steady-state harmonic tests are reported in Figure 9(a), where also the regression curve is shown. The corresponding variation of the equivalent stiffness is shown in Figure 9(b). It should be noted that it was not possible to reach the design displacement (130 mm) to avoid the damage of the steel superstructure.

On the basis of the above results, the points in Figure 10, representing the strength versus the maximum displacement of (half) isolation system of each test, were obtained calculating the strength as the product of the equivalent (secant) stiffness by the corresponding maximum displacement. Then, the regression curve was derived; in particular, the dashed part of the curve was extrapolated assuming a friction coefficient of about 6% for the sliders, to take into account the moderate value of pressure. For a useful comparison, the secant stiffness (= 220 kN/m) of a single elastomeric bearing was also shown, which was provided by the manufacturer (FIP Industriale S.p.A., Italy) together with equivalent viscous damping of about 15% (see Section 2) on the basis of qualification tests conducted by the same manufacturer for many elastomeric bearings with similar material characteristics. It is evident that, especially for rather low values of displacement (first branch of the regression curve), is much lower than the equivalent stiffness of (half) isolation system (see also Table 6), which includes also the contribution of (two) sliding bearings.

To check the reliability of the viscoelastic (VE) model of the isolated structure in simulating the response under steady-state forced and following free vibrations, the isolated structure was idealized as a 2-DOF system, assuming the damping matrix as a linear combination of mass matrix and stiffness matrix with reference to the two vibration modes (Rayleigh damping). Then, the experimental and numerical responses of the isolation system and superstructure were compared: for example, with reference to characterization test 4 (), the curves are shown in Figure 11.

As expected, the response of the isolation system was described with good accuracy, but the experimental response of the superstructure was underestimated. This can be in part ascribed to the very low value of the damping factor of the actual steel frame, especially in comparison with the damping factor identified for the isolation system, including also the effects of the friction of the sliders.

4. Shaking Table Tests of the Isolated Structure

4.1. Tests’ Inputs

A set of seven waveforms, which are compatible with the new Italian Seismic Code (NTC 2008) [10], was selected from the European Strong-Motion Database (Ambraseys et al. [11]) using REXEL v3.4 beta (Iervolino et al. [12]) for the DPC-ReLUIS research project. This selection is representative of regions in Italy with a moderate to high seismic risk. As a geometry scale factor = 1/3 and an elastic moduli scale factor = 1 were assumed to satisfy the dynamic similitude requirements, the selected earthquakes were compressed in time by a time scale of 1/√3. The 5% damped-scaled horizontal spectra are shown in Figure 12. The ground motion specifics relative to the original and scaled records are provided in Table 7.

The selected horizontal accelerograms are in compliance with the Italian Seismic Code for the life safety limit state of a strategic structure (functional class IV [10]) located in Naples, Italy (14.2767° longitude, 40.863° latitude), on soil type A (stiff soil or rock) with a nominal life of 100 years (which corresponds to a 1898-year return period according to the code). Further details about the ground motion selection can be found in a shaking table investigation by Calabrese et al. [13].

The three ground motions labelled as LAZ, CAM, and CAT in Table 7 were selected, among the seven waveforms mentioned above, for this study. For brevity, in the following discussion the attention is focused on the results obtained under the two records CAM and CAT, labelled also as motions 290 and 287, which induced displacements larger than those due to record LAZ. In particular, different intensities were considered increasing proportionally the acceleration of the records CAM and CAT: 290@100% and 290@150%; 287@100%, 287@150%, and 287@175%.

4.2. Analytical Modelling of the Isolated Structure

The numerical simulations have been performed using SAP2000 [14]. Columns and girders were idealized by an elastic beam model, while the isolation system was idealized using alternatively each of the following analytical models: viscoelastic (VE), bilinear (BL), or trilinear (TL) (Figure 13). The pin connection at the top of the columns was also considered in the structural model. In particular, when using BL and TL models, the damping for the superstructure was considered negligible in comparison to that of the isolation system model.

4.3. Results of Investigation

The experimental results obtained for the isolated structure subjected to each of the selected motions (in particular, 290 and 287 of different intensity), which were applied to the shaking table, were compared with the numerical response obtained using, one at a time, the three considered models (VE, BL, and TL) of the isolation system. For brevity, the main results are reported in Figures 1420, where the numerical curves were obtained by a suitable calibration of the characteristic parameters (i.e., , , , , and ) of half isolation model, consisting of one of the two elastomeric bearings and two of the four sliders.

More precisely, the numerical curves assuming VE model are shown in Figure 14; the numerical curves assuming a BL model are shown in Figure 15, while the analogous curves assuming a TL model are shown in Figures 16, 17 and 18 (motion 287), and Figures 19 and 20 (motion 290). In particular, all the curves for TL isolation model were obtained assuming the same values of the characteristic parameters of this model, to check the reliability of the model under different waveform and intensity of the motions.

As can be observed, the VE model, at least in the range of displacements measured during the shaking table tests, was capable of simulating with good accuracy the response of the isolation system, providing that a suitable calibration of the model was adopted. It should be noted that this calibration requires an iterative procedure, because an equivalent viscous damping ratio can be defined with reference to a steady-state response assuming a value of the expected maximum displacement, which is initially unknown. However, the numerical results for the superstructure, omitted for brevity, emphasized an underestimation of the experimental displacement. This may be expected because, assuming a proportional viscous damping matrix (Rayleigh damping), the relative displacement of the superstructure is affected by the high damping of the isolation system (15% at the design displacement), which is relatively high in comparison with the rather low damping of the superstructure (about 0.65%).

On the other hand, although the performed tests are limited and do not allow a general conclusion, it can be observed that BL and TL models overestimated the peak response of the isolation system (even about 40%); however, they underestimated that of the superstructure (even about 35%), as noted above for VE model. In addition, their calibration, especially for TL model, was more complex due to a greater number of parameters involved in comparison to the two parameters (i.e., equivalent stiffness and damping factor with reference to the expected maximum displacement) required to identify the VE model. However, it should be noted that, for displacements larger than those investigated in this study, BL and TL models may be more suitable.

4.4. Effectiveness of the Isolation System

To check the effectiveness of the isolation system, the experimental response of the isolated structure was compared with the numerical (undamped) response of the fixed-base structure, which, as already noted, presented very low damping (about 0.65%) and behaved elastically. A summary of the results is reported in Table 8, where the effectiveness of the isolation system is proved by reduction factor values rather lower than 1. It should be noted that even though the reduction factor is calculated with reference to the interstorey drift of the steel superstructure, supposed to be isolated or fixed-base, the same reduction can be assumed for the stresses because of the elastic behaviour of the steel structure.

5. Conclusions

The behaviour of the isolated structure equipped with an in-parallel combination of steel-PTFE sliding bearings and elastomeric bearings was tested under both controlled-displacement (harmonic) motion and earthquake ground motions of different intensity.

The first set of tests allowed the characterization of the isolation system, in particular its force-displacement relationship. Modelling the isolated structure as a 2-DOF system with VE behaviour (Rayleigh damping), the experimental displacement time-history (steady-state and free vibrations) was described with good accuracy for the isolation system, but it was underestimated for the superstructure due to the very low damping of the actual steel framed structure.

A further objective was to evaluate the reliability of different numerical models of the isolation system (VE, BL, and TL, commonly used) in simulating the dynamic response of the examined structure. The comparison between experimental and numerical curves showed that the VE model, at least in the range of displacements measured during the shaking table tests, was capable of simulating with good accuracy the response of the isolation system, provided that a suitable calibration of the model was adopted. On the other hand, BL and TL models overestimated the peak response of the isolation system. As expected, all the isolation models underestimated the response of the steel superstructure, which, as said above, actually presented very low damping.

Finally, the effectiveness of the isolation system was shown comparing the experimental response of the isolated structure with the numerical response of the fixed-base steel structure, whose damping was very low (0.65%).

Conflict of Interests

The authors declare that there is no conflict of interests regarding the publication of this paper.

Acknowledgments

The work is part of a research which has been supported by the consortium ReLUIS (Italian network of earthquake engineering laboratories) with a grant by the Italian Emergency Agency (2010–2013 ReLUIS Executive Project-Task 2.3.2-Development of New Technologies for Seismic Mitigation). The support of all the organizations is gratefully acknowledged. The steel-PTFE sliding bearings and elastomeric bearings were manufactured and provided for free by FIP Industriale S.p.A. (Padova, Italy). The company is gratefully acknowledged.