Forecasting of Energy Production for Photovoltaic Systems Based on ARIMA and ANN Advanced Models

Table 9

Main results of the energy production by the experimental PV park from Grojdibodu forecasted for the period 01-09.08.2013.

Day123456789

Hours when the inverter is running (solar  W/m2)13.7513.2513131313.25131313
Total 26,56525,59925,11625,11625,11625,59925,11625,11625,116
Total solar irradiance (Wh/m2)6,103.67,240.37,416.66,0917,388.087,101.347,214.137,285.47,325.3
Exported active energy (MWh)50.7759.4860.7448.4960.1856.625959.1659.54
PR (%) calculated in SCADA83.5182.5582.2279.9981.8380.0782.1281.5481.66
Real availability (%)10010010097.598.8498.11100100100
Availability given by the manufacturer (%)10010010097.598.84100100100100
Events in which energy production is disruptedInverter off 6 hoursInverter: motherboard damaged (replaced)Inverter off 15 min
String hours with energy loss627.9291.34483.82
Estimated energy losses (MWh)1.80.41.75