An Improved Solar Cooling System for Date Safety and Storage under Climate of the Maghreb

Table 3

Stored goods conditions and cold room features.

Cold room calculationStored goods

Storage conditions0°C/RH 85%
Freezing point-1°C
Specific heat (PT/NT)3.53/1.85 kJ/(kg·K)
Latent heat266.8 kJ/kg

Cold room features
Ambient conditions37.5°C/20.2°C WT
Cold room internal volume48 m3
Internal sizes
Isolation thickness150 mm
Heat transmission rate0.025 W/(m·K)

(1) Goods refrigeration loads537840 kJ/day
Goods rotation1200 kg at 25°C each 24 hours105840 kJ/day
Packaging cooling96000 kg/day432000 kJ/day

(2) Transmission heat gain45092 kJ/day
Walls31035 kJ/day
Roof6835 kJ/day
Floor6424 kJ/day
Door798 kJ/day

(3) Air renewal heat gain31908 kJ/day
Air renewal rate

(4) Internal loads heat gain155779 kJ/day
People272 W
Lighting540 W
Defrosting198 W
Evaporator fans793 W

Total cooling needs770619 kJ/day
Security margin10%
Compressor operation time per day24 h

Cooling capacity needed9811 W

Recommended unit (horizontal version series-SH-QF)MSF-QF 9136

Split units with silent condensing unit and cubic evaporating unit, designed for the preservation of generic products at positive or negative temperature in or negative temperature in medium size cold rooms. The condensing units are designed to be installed outdoors, with too low noise emission level due to silent design and tropicalized battery. MSF-QF 9136 owns compressor with 400 V-III and frigorific powers of 10260, 12300, 14500, and 17050 W for volumes of cooling compartments of 160, 220, 320, and 500 m3, respectively [55].